CHECK OPERATION
Before starting the system to check operation of low ambient
temperature control, ensure that the power wiring and location of
control assembly are correct. To check operation of low ambient
temperature control:
1. Turn power on to system.
2. Set thermostat below room temperature.
3. Ensure that there is the standard 3 --minute time delay for the
microprocessor controlled high wall fan coil systems.
4. Check time delay of installed accessories:
Under--ceiling (40QAC/QAQ) fan coils using the duct-- free
24--v thermostat delay settings: 2 or 4 minute delay.
The outdoor-- fan motor will not operate until the condensing
pressure reaches the control set point of 295 psig for
38MVC/MVQ models or 362 psig for 38QRF-- 018--036 and
38QRR-- 018--060 models (± 10 psig). When the set point is
reached, the outdoor fan will cycle to maintain the set point
condensing pressure.
If the low ambient temperature control does not operate correctly:
S Ensure that power is being supplied to the system.
S Check condensing pressure: if condensing pressure is below 255
psig for 38MVC/MVQ models or 321 psig for 38QRF-- 018-- 036
and 38QRR -- 018-- 060 models, the outdoor--fan motor should be
off and there should be no voltage across the 2 blue fan power
leads coming out of the control. If condensing pressure is about
295 psig or greater for 38MVC/MVQ models or 362 psig for
38QRF--018 --036 and 38QRR-- 018--060 models, the
outdoor-- fan motor should be on and will cycle off at around
255 psig for 38MVC/MVQ or 321 psig for 38QRF -- 018--036
and 38QRR -- 018--060 models.
Copyright 2008 CAC / BDP S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: IIK--53DS900--06
Replaces: AG--53DS900--01
Printed in U.S.A. Edition Date: 0 2/08