6. Mount electrical box to plenum or casing using 2 No. 10-24 X 1/2-in. sheet metal screws. (See Fig. 1.)
7. Mount evaporator freeze thermostat to side of electrical box using 2 No. 8-32 X 1/2-in. sheet metal screws.
8. Route wires for bulb through knockout hole in electrical box, and connect to evaporator freeze thermostat.
9. Wire evaporator freeze thermostat in series with Y low-voltage wire from indoor thermostat at indoor unit. (See Fig. 2.)
10. Secure cover to electrical box.
11. Insulate evaporator freeze thermostat bulb.
Fig. 1—Mounting Thermostat on Coil Casing
A97510
3
16-IN.
HOLES
TO CONTROL
WIRING
Fig. 2—Evaporator Freeze Thermostat Wiring
A97511
C
EVAPORATOR
FREEZE THERMOSTAT
Y
INDOOR
THERMOSTAT
OUTDOOR
CONTACTOR
© 1997 CAC/BDP P.O. Box 70, Indianapolis, IN 46206 agaaft02
—2—
Book/Tab: 1/3a, 4/2a Catalog No. 63AA-FT0